Data Center Census Near me

Calculator

How loud is a data center from my house?

Pick a published noise figure for data center equipment, enter your distance, and see an upper-end estimate of the sound level at your home, next to everyday sounds and the local limits.

From the nearest equipment, not the property line. 1 foot to 10 miles.

Sources add together: two equal sources are 3 dBA louder than one, ten are 10 dBA louder.

This only selects which local noise rules to compare with. It does not set the sound level, which comes from the source above.

Estimated level at your distance49 dBAFrom Modeled level at a specific receptor for one proposed campus: 3-building data center campus, nearest homes at 4th Street (Indiana), 49 dBA at 3,200 ft. About like: quiet daytime in a suburban area (40–50 dBA).
Falls to 45 dBA at about5,050 ftin the free-field model
Falls to 35 dBA at about16,050 ftin the free-field model

Read this as an upper-end estimate. It uses point-source spherical spreading in open air (L2 = L1 − 20·log10(d2/d1)) and ignores terrain, buildings, walls, barriers, trees and air absorption, which usually make the real level lower. Several sources add together, and low-frequency sound travels further than the dBA number suggests. It is not a substitute for a noise study.

Local noise limits that apply

Choose a project above to compare the estimate with the noise rules for its county or city. All tracked limits are listed further down this page.

Estimated sound levels at common distances

For each published figure, the free-field estimate at distances from 250 feet to a mile. Each row starts from a level and distance stated by its source; click a row to read the source.

Source (published figure)Published level250 ft500 ft1,000 ft2,000 ft1 mile
Diesel backup generator, Cummins C3500 D6E (3.5 MW), Level 1 sound-attenuated walk-in enclosure
Manufacturer sound data used as a model input in a data center acoustic study (not a field measurement) · Shen Milsom & Wilke, LLC for Equinix (Village of Minooka Planning and Zoning, Sept 9 2025), 2025
Source excerpt
“Cummins Generator C3500 D6E, 3500 kW: Sound pressure Leve of 87 dBA at 23 feet with a Level 1 sound-attenuated walk-in enclosure.”
87 dBA at 23 ft6660544840
Diesel backup generator, up to 2.75 MW class, upgraded enclosure
Vendor-provided rating (expected value) used as a model input in a preliminary sound study · Ramboll for Kimley-Horn (posted by Fairfax County Sully District), 2023
Source excerpt
“Vendor provided sound power level for emergency power generators with upgraded enclosures, based on expected sound pressure level rating of 75 dBA at 23 feet.”
75 dBA at 23 ft5448423628
Diesel backup generator, 3 MW, standard-noise enclosure
Design specification target for a planned campus (not measured) · Shiner Acoustics, LLC for Prologis (City of Yorkville, IL document center), 2025
Source excerpt
“Standard-noise units will be specified to meet 85 dBA at 23 ft and low-noise units will be specified to meet 75 dBA at 23 ft.”
85 dBA at 23 ft6458524638
Diesel backup generator, 3 MW, low-noise enclosure
Design specification target for a planned campus (not measured) · Shiner Acoustics, LLC for Prologis (City of Yorkville, IL document center), 2025
Source excerpt
“Standard-noise units will be specified to meet 85 dBA at 23 ft and low-noise units will be specified to meet 75 dBA at 23 ft.”
75 dBA at 23 ft5448423628
Diesel backup generator, Kohler KD2500-A (about 2.5 MW class)
Equipment sound pressure level listed as a model input (generator maintenance scenario) in an acoustic study · Ramboll for STREAM U.S. Data Centers LLC (GCEDC SEQR application, rev. Feb 18 2026), 2026
Source excerpt
“Generator Maintenance 75 dBA @ 7m 1 Generator per building”
75 dBA at 23 ft5448423628
Diesel backup generator set (56 planned), sound-attenuating enclosure
Sound data provided for a conceptual layout; table lists the 85 dBA level as likely to be achieved with a sound-attenuating enclosure · Epsilon Associates for DC Blox / Langan, 2026
Source excerpt
“85 dBA at 7 meters (Sound Pressure Level) likely to”
85 dBA at 23 ft6458524638
Air-cooled free-cooling chiller, Vertiv Liebert AFC CIZ125 (about 386 tons)
Manufacturer datasheet; preliminary data at nominal capacity (95 F ambient) · Vertiv Group Corp., 2024
Source excerpt
“Sound Level, dB(A) 82.2 83.1 82.6 82.7 … Sound Pressure Level (SPL) calculated at 3.3ft (1m) distance”
82 dBA at 3 ft4539332718
Loading dock and trash pick-up trucks at a proposed 200,000 sq ft data center (not cooling equipment)
Typical level stated in a CEQA noise analysis (Leq) · Kimley-Horn and Associates (CEQA document, CEQAnet), 2024
Source excerpt
“The typical loading dock/trash pick-up noise level is approximately 64 dBA Leq at 50 feet.”
64 dBA at 50 ft5044383224
Modeled level at a specific receptor for one proposed campus: 3-building data center campus, nearest homes at 4th Street (Indiana)
Modeled (CadnaA/ISO 9613), full-load normal operation incl. emergency generators at full load; EPA-guideline comparison, no local ordinance · ERM for Justified DataPower, LLC (filed in Kentucky PSC case 2026-00115), 2026
Source excerpt
“4th Street (Indiana) 49 … 4th Street (Indiana) 3,200 feet / East”
49 dBA at 3,200 ft71*65*59*53*45
Modeled level at a specific receptor for one proposed campus: 3-building data center campus, nearest homes at River Road (Hawesville)
Modeled (CadnaA/ISO 9613), full-load normal operation incl. emergency generators at full load; EPA-guideline comparison, no local ordinance · ERM for Justified DataPower, LLC (filed in Kentucky PSC case 2026-00115), 2026
Source excerpt
“River Road (Hawesville) 46 … River Road (Hawesville) 4,400 feet / South”
46 dBA at 4,400 ft71*65*59*53*44
Modeled level at a specific receptor for one proposed campus: 3-building data center campus, nearest homes at Southwire Plant Road (Hawesville)
Modeled (CadnaA/ISO 9613), full-load normal operation incl. emergency generators at full load; EPA-guideline comparison, no local ordinance · ERM for Justified DataPower, LLC (filed in Kentucky PSC case 2026-00115), 2026
Source excerpt
“Southwire Plant Road (Hawesville) 45 … Southwire Plant Road (Hawesville) 5,700 feet / Southwest”
45 dBA at 5,700 ft72*66*60*54*46*

Estimated dBA at each distance from a single source, using the published figure and the spreading rule below. Upper-end, free-field estimates: real levels are usually lower. Rows labeled “modeled level at a specific receptor for one proposed campus” are whole-campus model results at one receptor; extrapolating such a result to other distances is rougher than for a single piece of equipment, because a campus is many sources spread over a site rather than one point. An asterisk marks a distance closer than the one the source measured, where the estimate is least reliable.

How those levels compare with everyday sounds

Decibels are logarithmic: every 10 dBA is roughly a doubling in perceived loudness, and every 3 dBA doubles the sound energy. Reference points from public agencies:

Everyday soundAboutSource
Whisper
Source excerpt
“Whisper 20 dB”
20 dBACalifornia Department of Transportation (Caltrans)
Quiet daytime in a rural area with no significant noise sources
Source excerpt
“Quiet daytime noise levels in rural areas with no significant noise sources might be in the 30 to 40 dBA range”
30–40 dBAFederal Highway Administration, U.S. DOT
Library
Source excerpt
“30 Library”
30 dBACalifornia Department of Transportation (Caltrans)
Quiet daytime in a suburban area
Source excerpt
“while quiet daytime noise levels in suburban areas might be in the 40 to 50 dBA range”
40–50 dBAFederal Highway Administration, U.S. DOT
Normal conversation
Source excerpt
“Normal conversation 60-70 dBA”
60–70 dBANational Institute on Deafness and Other Communication Disorders (NIH)
Heavy traffic at 300 feet
Source excerpt
“Heavy traffic at 300 feet 60”
60 dBACalifornia Department of Transportation (Caltrans)
Vacuum cleaner at 10 feet
Source excerpt
“Gas lawnmower, 100 feet 70 Vacuum cleaner at 10 feet”
70 dBACalifornia Department of Transportation (Caltrans)
Busy street traffic
Source excerpt
“Busy Street Traffic 70 dB”
70 dBACalifornia Department of Transportation (Caltrans)
Movie theater
Source excerpt
“Movie theater 74-104 dBA”
74–104 dBANational Institute on Deafness and Other Communication Disorders (NIH)
Motorcycles and dirt bikes
Source excerpt
“Motorcyles and dirt bikes 80-110 dBA”
80–110 dBANational Institute on Deafness and Other Communication Disorders (NIH)

What affects how loud a data center is

Cooling equipment

Backup generators and testing

Low-frequency hum

  • Loudoun County states that its existing noise ordinance was designed for loud or sudden noise and may not fully capture low frequency noise from data center campuses. (Loudoun County, VA)
    Source excerpt
    “The Loudoun County noise ordinance was generally designed to address loud, sudden, or nuisance noise and may not fully capture LFN.”
  • An environmental consultant for a Kentucky data center project cites an ANSI recommendation that low frequency noise be kept below 70 dBC and modeled the project against it. (ERM for Justified DataPower, LLC (filed in Kentucky PSC case 2026-00115))
    Source excerpt
    “The American National Standards Institute recommends that low frequency noise levels should be maintained below 70 dBC.”

Night-time and background noise

Tones and character of the sound

  • The same consultant explains that equipment with tonal noise (such as a hum) would be judged against a limit 10 dB lower under the Yorkville, Illinois code. (Shiner Acoustics, LLC for Prologis (City of Yorkville, IL document center))
    Source excerpt
    “If the facility were to contain equipment with tonal noise emissions, its sound levels would be compared to a much more stringent (10 dB lower) Yorkville noise code.”

Background noise

  • Pre-construction measurements at a rural Illinois site found average background (L90) levels of 39 to 42 dBA, a baseline against which new noise is judged. (Shiner Acoustics, LLC for Prologis (City of Yorkville, IL document center))
    Source excerpt
    “The measurements showed that environmental sound levels were moderate, with average baseline (L90) sound levels of 39 to 42 dBA.”

Several sources at once

  • An AWS noise assessment illustrates that adding a second identical source raises the combined level by about 3 dBA, which matters for campuses with many units. (Amazon Web Services (for City of Wilmington, OH permit process))
    Source excerpt
    “adding a second lawn mower next to the first would cause the sound level at the same 100-foot location to increase to 63 dBA.”

Local noise limits for data centers

Numeric noise limits written into ordinances and permit documents we track, each with the rule’s own wording.

JurisdictionLimitWhere measuredApplies toRule
Loudoun County
Virginia
55 dBAresidential property lineresidential properties receiving noiseLoudoun County Zoning Ordinance maximum sound levels and data center noise study requirements
The rule’s wording
“For residential properties, the maximum allowable sound level at the property line is 55 dBA”
Prince William County
Virginia
73 dBA daytimeindustrial areasnoise in industrial areasPrince William County noise ordinance amendment (data centers and industrial uses)
The rule’s wording
“It limits daytime noise in industrial areas to 73 decibels during the day and 68 at night.”
Prince William County
Virginia
68 dBA nighttimeindustrial areasnoise in industrial areasPrince William County noise ordinance amendment (data centers and industrial uses)
The rule’s wording
“It limits daytime noise in industrial areas to 73 decibels during the day and 68 at night.”
Bartow County
Georgia
65 dBA daytime (8 a.m.-6 p.m.)not stated in the quoted text (measured over any 30-minute period)data center soundBartow County data center ordinance
The rule’s wording
“65 decibels or more over any 30-minute period from 8:00 a.m. to 6:00 p.m., or 55 decibels over any 30-minute period from 6:00 p.m. to 8:00 a.m.”
Bartow County
Georgia
55 dBA nighttime (6 p.m.-8 a.m.)not stated in the quoted text (measured over any 30-minute period)data center soundBartow County data center ordinance
The rule’s wording
“65 decibels or more over any 30-minute period from 8:00 a.m. to 6:00 p.m., or 55 decibels over any 30-minute period from 6:00 p.m. to 8:00 a.m.”
Fairfax County
Virginia
60 dBA daytime (7:00 a.m. - 10:00 p.m.)receiving residential property (any point within the property affected)all sources (data centers included)Fairfax County Code Chapter 108.1 Noise Ordinance, Sec. 108.1-4-2 (maximum continuous sound levels)
The rule’s wording
“Residential Areas in Residential Districts 7:00 a.m. – 10:00 p.m. 60”
Fairfax County
Virginia
55 dBA nighttime (10:00 p.m. - 7:00 a.m.)receiving residential property (any point within the property affected)all sources (data centers included)Fairfax County Code Chapter 108.1 Noise Ordinance, Sec. 108.1-4-2 (maximum continuous sound levels)
The rule’s wording
“Residential Areas in Residential Districts 10:00 p.m. – 7:00 a.m. 55”
Fairfax County
Virginia
72 dBA daytime (7:00 a.m. - 10:00 p.m.)receiving industrial-district propertyall sourcesFairfax County Code Chapter 108.1 Noise Ordinance, Sec. 108.1-4-2 (maximum continuous sound levels)
The rule’s wording
“Industrial Districts 7:00 a.m. – 10:00 p.m. 72”
Fairfax County
Virginia
65 dBA nighttime (10:00 p.m. - 7:00 a.m.)receiving industrial-district propertyall sourcesFairfax County Code Chapter 108.1 Noise Ordinance, Sec. 108.1-4-2 (maximum continuous sound levels)
The rule’s wording
“Industrial Districts 10:00 p.m. – 7:00 a.m. 65”
Illinois
Illinois
55 dBA daytime (7 a.m. - 10 p.m.)receiving residential (Class A) propertycommercial/industrial sources incl. data processingIllinois Pollution Control Board, 35 Ill. Adm. Code Part 901 (property-line noise standards)
The rule’s wording
“The Illinois noise code limits noise from commercial to residential land uses for the daytime (about 55 dBA) and nighttime (about 44 dBA) periods.”
Illinois
Illinois
44 dBA nighttime (10 p.m. - 7 a.m.)receiving residential (Class A) propertycommercial/industrial sources incl. data processingIllinois Pollution Control Board, 35 Ill. Adm. Code Part 901 (property-line noise standards)
The rule’s wording
“The Illinois noise code limits noise from commercial to residential land uses for the daytime (about 55 dBA) and nighttime (about 44 dBA) periods.”
Yorkville
Illinois
60 dBA daytime (7:00 a.m. - 10:00 p.m.)receiving residential propertyall sourcesYorkville city noise code (Title 4 Ch. 4)
The rule’s wording
“The Yorkville noise code limits noise to residential land uses for the daytime (60 dBA) and nighttime (50 dBA) periods.”
Yorkville
Illinois
50 dBA nighttime (10:00 p.m. - 7:00 a.m.)receiving residential propertyall sourcesYorkville city noise code (Title 4 Ch. 4)
The rule’s wording
“The Yorkville noise code limits noise to residential land uses for the daytime (60 dBA) and nighttime (50 dBA) periods.”
Wilmington
Ohio
60 dBA daytime (not stated in report)receiving residential landdata centers (ordinance cited for the CMH165 site)Wilmington Ordinance No. O-24-70, Section 1.2.c
The rule’s wording
“Section 1.2.c provides a 60 dBA daytime and 55 dBA nighttime sound level limit applicable at receiving residential land.”
Wilmington
Ohio
55 dBA nighttime (not stated in report)receiving residential landdata centers (ordinance cited for the CMH165 site)Wilmington Ordinance No. O-24-70, Section 1.2.c
The rule’s wording
“Section 1.2.c provides a 60 dBA daytime and 55 dBA nighttime sound level limit applicable at receiving residential land.”
Monterey Park
California
55 dBA daytime (7:00 am - 10:00 pm)residential receptors (presumed ambient)all sources (applied to a proposed data center)Monterey Park Municipal Code Sec. 4.50.080 (presumed ambient levels)
The rule’s wording
“Section 4.50.080 lists presumed ambient levels of 55 dBA during the day (7:00 am to 10:00 pm).”
Monterey Park
California
50 dBA nighttime (10:00 pm - 7:00 am)residential receptors (presumed ambient)all sources (applied to a proposed data center)Monterey Park Municipal Code Sec. 4.50.080 (presumed ambient levels)
The rule’s wording
“Section 4.50.080 lists presumed ambient levels of 50 dBA at night (between 10:00 pm and 7:00 am).”

17 numeric limits from 8 rules in the rules tracker. Limits differ in what they measure (a property line, a residence, a zoning boundary), in the averaging period and in which uses they cover, so a number here is not directly comparable with the estimate above unless the “where measured” matches your situation.

How the estimate works and its limits

The math
Sound from a single compact source drops 6 dBA each time the distance doubles (20 dB per tenfold): L2 = L1 − 20·log10(d2/d1). Several sources combine by adding energy: 10·log10(sum of 10^(L/10)).
Why it is an upper end
The rule assumes open, flat ground with nothing in the way. Real sites have buildings, walls, berms, trees and terrain that usually reduce sound, plus air absorption over long distances. Wind, temperature layers and reflections can occasionally raise levels. Where a source figure is a limit rather than a measurement, nothing here says the equipment reaches it.
What is not modelled
Frequency (low-frequency hum is hard to block and is heard indoors), tones, time of day, how many units run at once, and background noise at your home. A level that is lower than the background where you live may still be audible if it is tonal.
Where the figures come from
Every level in the dropdown is a number a published study, filing or regulator document states, with the distance it states. Nothing is guessed. No tracked project record yet publishes a sound level together with a distance, so project levels are not offered as a source; the project picker only brings up the local rules and any limits the project has committed to. A project’s own figure is added automatically once its record carries a noise_dba fact with a distance.

Data center noise: common questions

Are data centers loud?

It depends on the equipment and the distance. Published figures in this tool range from 45 dBA to 87 dBA, each measured or modelled at a stated distance (11 figures). Cooling equipment runs continuously, and an acoustic consultant for a proposed Illinois data center states that its air-cooled chillers run around the clock and that their sound output changes with load and outdoor temperature.

How loud is a data center?

Modeled level at a specific receptor for one proposed campus: 3-building data center campus, nearest homes at 4th Street (Indiana): 49 dBA at 3,200 ft (Modeled (CadnaA/ISO 9613), full-load normal operation incl. emergency generators at full load; EPA-guideline comparison, no local ordinance), according to ERM for Justified DataPower, LLC (filed in Kentucky PSC case 2026-00115). Use the calculator above to estimate the level at your distance.

How far away can you hear a data center?

It depends on the source and the surroundings. As arithmetic only: a source published at 49 dBA at 3,200 ft falls to about 45 dBA, roughly the level of a quiet room, at around 5,050 ft in the free-field model, which ignores barriers, buildings and terrain. Low-frequency sound can carry further than the dBA number suggests (Loudoun County, VA).

Are data center generators louder than the cooling equipment?

Published generator figures are among the highest in this tool: Diesel backup generator, Cummins C3500 D6E (3.5 MW), Level 1 sound-attenuated walk-in enclosure at 87 dBA at 23 ft (Manufacturer sound data used as a model input in a data center acoustic study (not a field measurement)), according to Shen Milsom & Wilke, LLC for Equinix (Village of Minooka Planning and Zoning, Sept 9 2025). A noise assessment for a planned Illinois campus assumes each backup generator is exercised for 30 minutes a month on weekday daytime hours. Backup generators run mainly during tests and outages, while cooling equipment runs continuously.

Is it safe to live near a data center?

WHO/Europe describes noise as a public health issue with negative impacts on health and well-being. This tool estimates sound levels only. For air emissions, electromagnetic fields and other health questions, see our guide: Are data centers bad for your health? Check the permits and noise study for the project near you.

What noise limits apply to data centers?

Limits are set locally. 17 numeric limits from 8 rules are tracked here, for example Loudoun County sets 55 dBA (residential property line). Pick a project in the calculator to see the rules for its jurisdiction.

Related: Are data centers loud? · Are data centers bad for your health? · Local data center rules · Projects near a ZIP code · Impact calculator

Cite this page

Last updated Oct 13, 2026. Figures may change as records are updated — include the date you retrieved them.

APAData Center Census. (2026). Data center noise estimator. Retrieved from https://datacentercensus.com/noise
MLA“Data center noise estimator.” Data Center Census, Oct 13, 2026, https://datacentercensus.com/noise.
Linkhttps://datacentercensus.com/noise

Republishing a figure or table? Attribute it to Data Center Census with a link to this page. The underlying data is downloadable as JSON and CSV; the press kit has standing figures and contact details.