Explainer
Are data centers bad for your health?
25 cited sources, newest dated Sep 14, 2026 · Census figures as of Sep 23, 2026
Short answer
A data center itself does not emit much; its engines do. EPA says the primary pollutants from internal combustion engines are nitrogen oxides, hydrocarbons and other organic compounds, carbon monoxide and particulates[4], and that diesel engine pollutants are known or suspected of causing cancer and other serious health effects[5]. Those engines normally run only for testing and emergencies: Virginia’s auditors calculated data center diesel generators make up less than 4% of regional nitrogen oxide emissions in Northern Virginia[1]. Researchers estimate a national public health burden anyway, and regulators are now monitoring the question directly[2][6].
- of Northern Virginia nitrogen oxide emissions from data center generators, per JLARC[1]
- <4%
- premature deaths a year by 2030 estimated in a Caltech-reported study[2]
- ~1,300
- IARC classification of diesel engine exhaust (carcinogenic to humans)[3]
- Group 1
Air: what the engines emit
Most data centers keep diesel generators for backup. EPA’s AP-42 emissions-factor guidance says the primary pollutants from internal combustion engines are nitrogen oxides, hydrocarbons and other organic compounds, carbon monoxide and particulates[4], and for gas turbines, nitrogen oxides and carbon monoxide, and to a lesser extent volatile organic compounds[7]. An EPA fact sheet on stationary engine standards says pollutants emitted from diesel engines are known or suspected of causing cancer and other serious health effects, including aggravation of respiratory and cardiovascular disease[5]. In June 2012 the World Health Organization’s cancer agency classified diesel engine exhaust as carcinogenic to humans, based on sufficient evidence of increased lung cancer risk[3].
What those emissions do at ordinary exposure levels is well documented. EPA says numerous studies link particle pollution to premature death in people with heart or lung disease, nonfatal heart attacks, irregular heartbeat and aggravated asthma[8], with children, older adults, people with heart or lung disease, minority populations and low-income populations most likely to be affected[8]. Nitrogen dioxide, which comes primarily from burning fuel, can irritate airways[9].
The exposure question is how often the engines run. Virginia’s JLARC reported nearly all current data centers use Tier 2 diesel generators, which the state allows to run only in emergencies or for testing[1], and calculated their share of regional nitrogen oxide emissions at under 4%[1]. That boundary has been tested: EPA issued a clarification in May 2025 that certain engines can run up to 50 hours a year in non-emergency conditions to supply power to the grid[10], engine hours run under DOE emergency orders do not count toward that 50[11], and Data Center Knowledge reported in May 2026 that Virginia DEQ concluded generators permitted as emergency units will be operated for extended periods[12]. Virginia has since begun requiring Tier 4-equivalent standards for new or modified data center generators[13].
What researchers estimate
In a December 2024 piece titled “Air Pollution and the Public Health Costs of AI,” Caltech reported estimates of as many as 1,300 premature deaths a year in the U.S. by 2030, with total public health costs approaching an estimated $20 billion a year[2]. The same piece says backup generators create regional public health costs of some $190 million to $260 million a year, rising tenfold to $1.9 billion to $2.6 billion if they emitted at their maximum permitted level[2]. A later version of that work, now titled “Health-Informed Computing” and listed as accepted by Communications of the ACM (June 2026), projects the total annual public health burden of U.S. data centers[14].
These are modeled estimates of a national total, not measurements at any one site. Virginia DEQ is running a data center air monitoring project, funded by an EPA grant, in response to data center growth in Northern Virginia and citizen concerns about emissions from backup generators and natural gas turbines[6].
On-site gas turbines
Some AI campuses now generate their own power on site, which changes the emissions picture from occasional testing to continuous operation. EPA says stationary combustion turbines and engines, common primary and backup power sources for data centers, are subject to federal standards[11], and that state and local air agencies issue most air permits for data centers under EPA-approved programs[11].
The clearest example is Memphis. Action News 5 reported in July 2025 that the Shelby County Health Department’s approval of xAI’s natural gas-fired turbines includes caps on the facility[15]; Tennessee Lookout reported the NAACP and another group appealed that air permit for 15 gas turbines[16], and that according to the appeal the campus had up to 35 gas turbines on site capable of more than 420 MW before it sought the permit[16]. The Southern Environmental Law Center, which opposed the permit, says methane gas turbines release smog-forming pollution and chemicals like formaldehyde, which it ties to asthma, respiratory illness, heart problems and some cancers[17] (an advocacy claim).
Noise
WHO/Europe said when releasing its 2018 environmental noise guidelines that noise is one of the top environmental hazards to physical and mental health and well-being in the European Region[18] — though those guidelines cover transportation, wind turbine and leisure noise, not data centers[19]. EPA says studies have shown direct links between noise and health, including stress-related illnesses, high blood pressure, speech interference, hearing loss and sleep disruption[20]; since 1981, primary responsibility for noise has sat with state and local governments after EPA’s noise office was closed[20].
For data centers specifically, JLARC found the noise is not loud enough to damage hearing and rarely loud enough to violate ordinances, but that its constant nature has sometimes been a problem near homes[1]. Our noise guide has the decibel limits localities have adopted.
Power lines and EMF
Concerns about electromagnetic fields usually attach to the transmission lines built to serve a campus rather than the building. WHO’s 2007 backgrounder describes a consistent pattern of a two-fold increase in childhood leukaemia associated with average residential power-frequency magnetic field exposure above 0.3 to 0.4 microtesla[21], while concluding that, on balance, the evidence related to childhood leukaemia is not strong enough to be considered causal[21]. WHO said in 2016 that despite extensive research there is no evidence to conclude that exposure to low-level electromagnetic fields is harmful to human health[22], and the National Cancer Institute says no consistent evidence for an association between any source of non-ionizing EMF and cancer has been found[23].
Fire and battery safety
The most serious recent incident was a battery fire, not an emissions event. The Korea Herald reported that a fire at South Korea’s National Information Resources Service data center in Daejeon started when lithium-ion batteries in its uninterruptible power supply caught fire[24], and Uptime Institute said the fire began when one of the basement battery packs entered thermal runaway, resulting in an uncontrolled fire[25].
What the Census record shows
In the Census, 25 projects publish what backup generation they plan, 21 have a documented air permit, and 11 record how close the nearest homes or schools are. See the power and generation tracker.
Common questions
Are data centers bad for your health?
The buildings themselves emit little; the engines do. EPA says diesel engine pollutants are known or suspected of causing cancer and other serious health effects, and IARC classifies diesel exhaust as carcinogenic to humans. In practice exposure depends on how often engines run: Virginia’s auditors put data center generators at under 4% of regional nitrogen oxide emissions in Northern Virginia.
Do data centers cause air pollution?
Backup diesel generators and, increasingly, on-site gas turbines emit nitrogen oxides, carbon monoxide, particulates and volatile organic compounds, according to EPA emissions-factor guidance. Virginia DEQ is running an EPA-funded air monitoring project in Northern Virginia in response to resident concerns.
Can living near a data center make you sick?
There is no measurement-based finding that living near a typical data center causes illness. Research estimates a national public health burden from data center air pollution, and Virginia’s auditors found noise is rarely loud enough to violate ordinances but its constant nature has been a problem near some homes.
Are the power lines near data centers dangerous?
WHO describes a consistent statistical pattern linking higher residential magnetic fields to childhood leukaemia but concluded the evidence is not strong enough to be considered causal, and says there is no evidence that low-level electromagnetic fields are harmful. The National Cancer Institute reports no consistent evidence of an association with cancer.
Sources
- Data Centers in Virginia (Report 598)Joint Legislative Audit and Review Commission (JLARC), Virginia General Assembly · 2024-12
4 source excerpts
“in Northern Virginia, they make up less than 4 percent of regional emissions of nitrogen oxides”
“Nearly all current data centers use 'Tier 2' diesel generators, which DEQ allows to run only in emergencies or as part of routine maintenance testing.”
“Data centers emit low-frequency noise that is not loud enough to damage nearby residents' hearing and rarely loud enough to violate noise ordinances.”
“The constant nature of data center noise has sometimes been a problem when data centers are located near residential areas.”
- Air Pollution and the Public Health Costs of AICalifornia Institute of Technology · 2024-12
2 source excerpts
“as many as 1,300 premature deaths per year by 2030 in the United States. Total public health costs from cancers, asthma, and other diseases, as well as from missed work and school days are approaching an estimated $20 billion per year.”
“creating regional public health costs of some $190 million to $260 million a year. If these backup generators emit at their maximum permitted level, the annual costs will increase tenfold and reach $1.9 billion to $2.6 billion.”
- IARC: Diesel Engine Exhaust Carcinogenic (Press Release No. 213)International Agency for Research on Cancer (WHO) · 2012-06-12
Source excerpt
“today classified diesel engine exhaust as carcinogenic to humans (Group 1), based on sufficient evidence that exposure is associated with an increased risk for lung cancer.”
- AP-42 Section 3.4: Large Stationary Diesel And All Stationary Dual-fuel EnginesU.S. Environmental Protection Agency · 1996-10
Source excerpt
“The primary pollutants from internal combustion engines are oxides of nitrogen (NOx), hydrocarbons and other organic compounds, carbon monoxide (CO), and particulates, which include both visible (smoke) and nonvisible emissions.”
- Fact Sheet: Final Amendments to Emission Standards (Stationary Engines)U.S. Environmental Protection Agency · 2013-01-14
Source excerpt
“Pollutants emitted from diesel engines are known or suspected of causing cancer and other serious health effects including: ... Aggravation of respiratory and cardiovascular disease ... Premature death in people with heart or lung disease”
- Data Center Air Monitoring ProjectVirginia Department of Environmental Quality · 2026
Source excerpt
“DEQ is conducting a special data center air monitoring project through a grant from EPA in response to the rapid growth of data centers in Northern Virginia and citizen concerns for emissions from back up generators and/or natural gas fired turbines at those data centers.”
- AP-42 Section 3.1: Stationary Gas TurbinesU.S. Environmental Protection Agency · 2000-04
Source excerpt
“The primary pollutants from gas turbine engines are nitrogen oxides (NOX), carbon monoxide (CO), and to a lesser extent, volatile organic compounds (VOC).”
- Health and Environmental Effects of Particulate Matter (PM)U.S. Environmental Protection Agency · 2026
2 source excerpts
“Numerous scientific studies have linked particle pollution exposure to a variety of problems, including: premature death in people with heart or lung disease ... nonfatal heart attacks ... irregular heartbeat ... aggravated asthma”
“People with heart or lung diseases, children, older adults, minority populations, and low socioeconomic status populations are the most likely to be affected by particle pollution exposure.”
- Basic Information about NO2U.S. Environmental Protection Agency · 2026
Source excerpt
“NO2 primarily gets in the air from the burning of fuel. ... Breathing air with a high concentration of NO2 can irritate airways in the human respiratory system.”
- EPA Issues Clarification to Help Power Data Centers, Ensure U.S. Is the AI Capital of the WorldU.S. Environmental Protection Agency · 2025-05-01
Source excerpt
“certain engines can operate for up to 50 hours per year in non-emergency conditions to supply power for our nation's grid”
- Clean Air Act Resources for Data CentersU.S. Environmental Protection Agency · 2026-09-14
3 source excerpts
“Therefore, any hours of engine operation pursuant to these emergency orders do not count toward the 50 hours that certain emergency engines are allowed to operate in non-emergency situations”
“Stationary combustion turbines and stationary engines – common sources of primary and backup power for data centers – are subject to various new source performance standards (NSPS) for certain air emissions and national emission standards for hazardous air pollutants (NESHAP).”
“State and local air agencies issue most air permits for data centers, under programs approved as meeting minimum requirements established by the CAA and EPA regulations.”
- Virginia DEQ Revises Data Center Generator Rules as Community Pushback BuildsData Center Knowledge · 2026-05-19
Source excerpt
“DEQ has also considered the permit history and operating profile for data center gen-sets that now strongly indicate that gen-sets permitted as emergency units will be operated for extended periods under certain circumstances.”
- Data Centers: Noise & Air Quality ConcernsLoudoun County, Virginia · 2026
Source excerpt
“On July 1, 2026, DEQ began mandating Tier 4-equivalent emissions standards for new or modified generators at data center sites.”
- Health-Informed Computing: Estimating and Addressing the Public Health Impact of Data Centers (arXiv:2412.06288v4)arXiv (Han, Wu, Li, Wierman, Ren) · 2026-06-08
Source excerpt
“the total annual public health burden of U.S. data centers up to more than $20 billion in 2028”
- Health dept. grants permit for xAI turbinesAction News 5 (WMC) · 2025-07-02
Source excerpt
“The health department's approval includes caps on the facility's 12-month rolling emission rates, which xAI is required to record and maintain monthly.”
- NAACP, others appeal xAI turbine permits for Memphis data centerTennessee Lookout · 2025-07-17
2 source excerpts
“The NAACP and another group are challenging the Shelby County Health Department's decision to grant xAI an air permit for 15 gas turbines at its South Memphis data center, according to an appeal filed Wednesday.”
“The groups allege that the campus had up to 35 gas turbines on site capable of generating more than 420 megawatts of electricity before it sought permits.”
- Memphis health leaders grant air permit for xAI data centerSouthern Environmental Law Center · 2025-07-02
Source excerpt
“Methane gas turbines release smog-forming pollution and harmful chemicals like formaldehyde. The pollutants are tied to asthma, respiratory illnesses, heart problems, and even certain types of cancer.”
- New WHO noise guidelines for Europe releasedWorld Health Organization Regional Office for Europe · 2018-10-10
Source excerpt
“one of the top environmental hazards to both physical and mental health and well-being in the European Region”
- Environmental noise guidelines for the European Region: executive summaryWorld Health Organization Regional Office for Europe · 2018
Source excerpt
“transportation (road traffic, railway and aircraft) noise, wind turbine noise and leisure noise”
- Clean Air Act Title IV - Noise PollutionU.S. Environmental Protection Agency · 2026
2 source excerpts
“Studies have shown that there are direct links between noise and health. ... stress related illnesses, high blood pressure, speech interference, hearing loss, sleep disruption, and lost productivity.”
“in 1981 the Administration concluded that noise issues were best handled at the State and local level. As a result, ONAC was closed and primary responsibility of addressing noise issues was transferred to State and local governments.”
- Exposure to extremely low frequency fields (Backgrounder)World Health Organization · 2007-06
2 source excerpts
“a consistent pattern of a two-fold increase in childhood leukaemia associated with average exposure to residential power-frequency magnetic field above 0.3 to 0.4 µT”
“Thus, on balance, the evidence related to childhood leukaemia is not strong enough to be considered causal.”
- Radiation: Electromagnetic fields (Q&A)World Health Organization · 2016-08-04
Source excerpt
“Despite extensive research, to date there is no evidence to conclude that exposure to low level electromagnetic fields is harmful to human health.”
- Electromagnetic Fields and CancerNational Cancer Institute (NIH) · 2022-05-30
Source excerpt
“Sources of ELF-EMFs include power lines, electrical wiring, and electrical appliances ... No consistent evidence for an association between any source of non-ionizing EMF and cancer has been found. ... The strength of a magnetic field decreases rapidly with increasing distance from its source.”
- Battery blaze at state data center casts shadow over ESS pushThe Korea Herald · 2025-09-28
Source excerpt
“The blaze at the National Information Resources Service in Daejeon started when lithium-ion batteries caught fire in the facility's uninterruptible power supply system. ... It took 22 hours to fully extinguish the fire.”
- South Korean data center fire sparks a stark reminder (Uptime Intelligence Update 429)Uptime Institute · 2025-11-04
Source excerpt
“One of the battery packs in the basement entered thermal runaway that resulted in an uncontrolled fire.”
Each source was opened and checked against the excerpt shown. Company statements are identified as such. Figures are as published; where sources differ, each is shown.
Cite this page
Last updated Sep 23, 2026. Figures may change as records are updated — include the date you retrieved them.
| APA | Data Center Census. (2026). Are data centers bad for your health. Retrieved from https://datacentercensus.com/guides/are-data-centers-bad-for-your-health |
|---|---|
| MLA | “Are data centers bad for your health.” Data Center Census, Sep 23, 2026, https://datacentercensus.com/guides/are-data-centers-bad-for-your-health. |
| Link | https://datacentercensus.com/guides/are-data-centers-bad-for-your-health |
Republishing a figure or table? Attribute it to Data Center Census with a link to this page. The underlying data is downloadable as JSON and CSV; the press kit has standing figures and contact details.